On 1 November 2026 a Chinese national standard took effect that does something no Chinese standard had done before. It names stainless steel pipe as an acceptable material for the refrigerant connection lines of multi-split air conditioning and heat pump systems, and it sets a minimum wall thickness for that pipe. The economics behind the decision are equally plain: the copper that such lines used to carry has become the expensive half of the system.
What took effect, and what it actually says
The document is GB/T 27941-2026, the standard for the design and installation of multi-split air conditioning and heat pump systems. It is a revision of GB/T 27941-2011, which it replaces in full rather than in part. The record below is taken from the two official Chinese national standard platforms, the National Standard Information Publicity Platform and the national standards full-text portal, both of which carry the same entry for this standard.
| Item | As published on the official platforms |
|---|---|
| Standard number | GB/T 27941-2026 |
| English title, translated from the Chinese title | Requirements for design and installation of multi-split air conditioning (heat pump) systems |
| Status | In force from 1 November 2026 |
| Published | 30 April 2026 |
| Effective | 1 November 2026 |
| Replaces | GB/T 27941-2011, in full |
| Plan number | 20250756-T-604 |
| CCS / ICS | J 73 / 27.200 (refrigeration technology) |
| Technical committee | National Refrigeration and Air-Conditioning Equipment Standardization Technical Committee (TC238) |
| Supervising authority | China Machinery Industry Federation |
| Issued by | State Administration for Market Regulation and Standardization Administration of China |
| Drafting units | 18 organizations, including Tsinghua University, Guangdong Midea HVAC Equipment, Haier, Hisense Hitachi, Daikin (China), TCL Air Conditioners (Zhongshan), Xiaomi Smart Home Appliance (Wuhan), China Tower, China Mobile Communications Group Design Institute, and one materials supplier, Wuhu Dajin New Materials, which joined the drafting as a materials party |
| Companion product standard | GB/T 18837-2026, multi-split air conditioning and heat pump units, published 30 April 2026 and effective the same day, replacing GB/T 18837-2015 |
The standard text itself is copyrighted and is not reproduced here. The substance below is taken from industry reporting published in October 2026 that summarises the drafting explanation, and it is worth reading with that caveat in mind. Two points are consistent across the reports. First, the connection pipe may now be stainless steel where it was previously expected to be copper, and the standard sets a minimum wall thickness for it. Second, the standard adds press-fit connection and flare fabrication requirements for that line, which is a joining-method change rather than a materials change.
| Change reported for the 2026 revision | What it means in practice |
|---|---|
| Stainless steel connection pipe permitted, with a minimum wall thickness specified | The first time a Chinese national standard has named stainless steel pipe for this duty |
| Press-fit connection and flare fabrication requirements added | Joining method becomes part of the installation standard, so the joint has to be designed into the line |
| R32 refrigerant brought into scope with its own application design and installation requirements | R32 is a flammable (A2L) refrigerant, so the safety requirements are the cost driver behind the switch |
| Method for determining indoor and outdoor unit capacity ratio added | System selection becomes quantifiable rather than a matter of designer judgement |
| System SEER, HSPF and APF calculation and evaluation methods added | Building energy performance, and therefore the specification, is now measured at system level |
| Refrigerant shut-off device and refrigerant concentration detection and alarm required on indoor units | New hardware on every indoor unit, which is where much of the quoted cost difference comes from |
| Connection pipe length, oil trap, thermal expansion compensation and additional refrigerant and oil charging detail expanded | Installation practice is specified more tightly than in the 2011 edition |
Why the material is changing now
Copper is the reason. Industry reporting in October 2026 puts domestic spot copper at around 73,800 yuan per tonne in early 2025, rising through the year and reaching a peak of about 111,400 yuan per tonne on the Yangtze spot market in 2026. Copper is reported to account for 20 to 30 percent of multi-split unit cost, and up to 35 percent on higher-end models. Brokerage estimates quoted in the same reporting put the gross margin effect of a 15, 30 and 50 percent copper price rise at 2.1, 4.2 and 7.1 percentage points respectively.
The substitution arithmetic is what makes it a pipe story. Reported material cost for the connection line falls from roughly the 200 yuan per metre level to the 60 to 70 yuan per metre level, which is about 200 yuan saved per unit. At an output of 500,000 units a year that is more than 100 million yuan. The same reporting is careful about the qualification, and so should any buyer be: the standard permits the substitution, it does not certify a particular product, and the reporting explicitly warns that a change of material must be declared rather than made silently, and that reliability of the substituted joint has to be demonstrated rather than assumed.
The wider stainless demand picture in the same week
Two dated market readings from the week of 19 to 23 October 2026 sit alongside the standard. On the stainless side, SMM’s weekly review records that the Shanghai futures contract for stainless steel rebounded 2.69 percent to 13,575 yuan per tonne on 23 October, its first weekly gain in three after a two-week slide, while 300-series social inventory fell 12,000 tonnes to 560,000 tonnes, the lowest reading since 12 February, and the finished-to-raw spread widened from 3.7 to 6.8 points. On the nickel side, SteelMint reported three-month LME nickel at 15,900 dollars per tonne on 23 October, up 4 percent week on week, with Chinese producers reported to be discussing output reductions at their Indonesian operations. Those reductions, covering 50 percent each for mixed hydroxide precipitate and high grade matte and 20 percent for nickel pig iron, were described as proposals considered from 23 October to the end of 2026 and not as confirmed decisions.
Demand growth in the wider sector is reported too. Industry analysis published on 28 October 2026 records that Chinese shipyards took 81.8 percent of global new shipbuilding orders in the first nine months of 2026, that green ship orders held 74.1 percent of the international share, and that stainless steel demand in shipbuilding and marine work is expected to grow about 11.8 percent in 2026, with LNG carriers, chemical carriers, scrubbers and methanol or ammonia fuel tanks pulling on 316L and duplex grades. The same analysis records Outokumpu Ultra 254 SMO supplied in excess of 2,000 tonnes for scrubber towers across more than 500 vessels.
What the standard does not settle
This is the part that matters to a pipe order. GB/T 27941-2026 fixes a minimum wall thickness and a joining method. It does not name an alloy for the stainless connection pipe, and it is not a material specification. For any line that leaves a Chinese factory under ASME Section II rather than under a Chinese installation rule, the alloy question is settled by the material specification and the certification question by the general requirements specification. SA-312 covers austenitic stainless pipe and SA-789 covers austenitic tubing of average wall thickness or of minimum wall thickness if that is specified on the order, while SB-444 covers cold-worked seamless nickel alloy pipe and tube. On the certificate itself, SA-999 requires a certificate of compliance that is dated and identifies the submitting organisation, and it states plainly that a signature or notarization is not required, while leaving the certifying organisation responsible for the content of the document whatever the signature position is.
What a buyer has to state on the order has not changed because a Chinese installation standard changed. Grade, product form, tests, marking and certification still have to be named, because silence on any of them leaves the decision with the mill. Our pipe and tube category page sets out the forms we supply, from our 316L seamless pipe range through the mechanical tubing catalogue that thin-wall instrumentation and connection lines use. If you want a material recommendation against a specific line, or a certificate format your client will accept, request a stainless pipe quotation and tell us the service, the joining method and the standard your contract names.
Related products: nickel alloy butt-weld elbows · nickel alloy equal and reducing tees · pipe fittings. Supplied to the applicable ASTM / ASME specifications with EN 10204 3.1 mill test certificates; confirm grade, size and quantity with our engineers.